illustrative picture
KPZ-1_PO
KPZ-1_PO
KPZ-1_PO
Lai piekļūtu 3D modeļu lejupielādei nepieciešama pieslēgšanās vai reģistrācija.
EAN kods8595568932358
Muitas kods85363030
Svars0.06 kg/pcs
MateriālsPP
Halogēnus nesaturošs materiāls
Bezšuvju materiāls
Pašnodziestošs30 s
Nominālais spriegums<= 400 V
Nominālā strāva<= 16 A
Temperatūras izturība-5 - 60 °C
Kvēlojošas stieples tests850 °C
Montāža
horizontally max. 3 pieces of boxes next to each other, vertically max. 2 pieces next to each other
Platums73 mm
Augstums68 mm
Dziļums47 mm
Frēzētās (urbtās) atveres diametrs73 mm
Ražotāja ieteikumi
Visam produktu sortimentam, kas paredzēts montāžai dobās sienās, iesakām izmantot mūsu piegādāto frēžu komplektus.
Uguns reakcijas klase materiālam uz kā tiek uzstādīts produktsA1 - F
Ļauj montēt dubultu kontaktligzdu
Aizsardzības pakāpeIP30
Saskaņā ar standartiemČSN EN 60 670-1, ČSN EN 1363-1:2013
Ugunsizturības standartiEI 15 - EI 120
Iepakojuma apraksts
the box is fitted with screws for fixing onto plasterboard and with instrument screws, pack loosely in a box

Wiring device box for fire partitions. Suitable for installation in plasterboard and aerated concrete structures. Designed for distribution with voltage up to 400 V. Inlet openings made of flexible material. Ensured airtightness of the passage even when the cable or pipe is inserted. Foaming material on the outside and inside of the box. In the event of a fire, this material quickly changes its volume (swells) and thus seals the installation opening of the box and prevents the passage of fire through the partition. The diameter of the installation hole is 73 mm. Mounting screws and metal feets are provided with a three-way thread for quick installation. Suitable for buildings with increased personal and property protection in case of fire. The box is available in selected countries.

Note for system with maintained functionality in fire:
Fire integrity and insulation up to 120 minutes (EI 15 - EI 120). The fire protection material inside and outside the box.
The PO classification is dependent on the specific placement of the box in plasterboard or aerated concrete, detailed in the new catalog – Systems with maintained functionality in fire.

Pašlaik nav produkti
Pašlaik nav produkti